Fires

2. Extinguishing Agents

2.2. Maintenance of extinguishers

A) Operations to be carried out by the user:

Every 3 months:

  • Check the accessibility, apparent good state of conservation, safety elements, tamper seals, inscriptions, hose, etc.
  • Check the load status (weight and pressure) of the extinguisher and the state of the mechanical parts (nozzle, valves, hose, etc.).

B) Operations to be carried out by specialised personnel from the manufacturing firm or installer:

Every year:

  • Verify the load status and, in the case of dry chemical extinguishers with an attached propellant cartridge, the status of the extinguishing agent.
  • Check the propellant pressure of the extinguishing agent.
  • State of the hose, nozzle or lance, valves and mechanical parts.

Every 5 years:

  • The manufacturer or distributor is to re-date stamp the extinguisher (three times) from the original date-stamping of the extinguisher.